SINTEF STF25 F95020
Test Programme F3 - Confined Jet and Pool Fires - Technical Report for Test PF10
BFETS Phase 2
FABIG Members: Log-in to access all FABIG resources LOG IN
SUMMARY
SINTEF Energy - Norwegian Fire Research Laboratory (NBL) has the task to carry out a series of fire tests with confined jet and pool fires, according to the test programme F3 of Blast and Fire Engineering for Topside Structures. This report is for pool fire test PF10.
The pool fire test PF10 represents a 24 m2 pool fire of condensate (a liquid fraction from an oil refinery) on a water bed in a 415 m3 enclosure.
The general fire behaviour such as flame geometry and characteristics, temperature field and heat load from this naturally ventilated fire was studied. The main purpose of pool fire test PF10 was to compare the difference between pool fire and jet fire (JF9, JF9B, JF9C) under equal conditions, and to investigate the scaling effect between 135 m3 and the 415 m3 compartment.
The fuel burning rate was ~0.63 kg/s. The ventilation opening was 9.7 m2 designated ventilation configuration V2. The fire became under-ventilated, with a variation of air-to-fuel equivalence ratio of 0.79±0.27.
This technical report includes description of the test rig, the experimental details and a set of curves from the measured parameters.